ReleaseNote_DELL_NMC_01_08_0001.txt Driver File Contents (DELL_NMC-UPS-FW--H910P-_A02_R286786.exe)

================================================================================
Release Note for Dell UPS Management Card (H910P).
Firmware  : Release 01.08.0001
Date : 10/08/2010  (english format)
EATON (c) 2009
================================================================================

Files Contained in the release package:

DELL_NMC_01_08_0001.bin – The binary image of the firmware for the Network Management 
Card (NMC) which can be loaded into the NMC using your Web Browser interface and the 
Firmware Upgrade option. Refer to the “Upgrading the Card's Firmware” section in NMC 
Manual for details on flash upgrading the Firmware.

MibUpsDell.mib - This Management Information Base (MIB) is a type of database used 
for managing the UPS in a communications network using optional software such as Dell
Management Console (DMC). The MIB comprises of a collection of objects in a (virtual)
database that are accessed by Network Management Software to analyze and display the data.


================================================================================

                              =========================
                                 Release 01.08.0001
                              =========================
                              
Improvements:

   - Alarm Communication with IPP
   - add a rescue menu during boot
   - KIGER-830: NMC FW change request: Factory & Reset Comm Button Move    
   - KIGER-832: UPS FW and NMC FW change request: IP address Display on LCD           
          
          
Corrected issues:

   - Correction of the loss of IP parameters.        
   - KIGER-831: NMC FW change request: Word Change " Inverter" to "On Battery"     
   - KIGER-836: File Download Pop-Up windows doesn't displayed when the user want to Save Log.   
   - KIGER-842: Unable to save authentication login/password for SMTP server under Firefox   
   - KIGER-843: Power loss when Shutdown after parameter is set lower than switch off after parameter on LS1 and LS2   
   - KIGER-850: DNS cannot be configured and as a result, the host name cannot be translated into IP addresses.   
   - KIGER-852: User is able to reset metrics without authentication    
   - KIGER-853: NMC sends emails which are not compliant with RFC 4.1.1.1.
   - KIGER-854: UPS trap with Specific Trap ID '62' is classified as unknown in event console.          
   - KIGER-855: Missing values descriptions  in the Mib file definition for physicalBatteryTestStatus.      
   
   
--------------------------------------------------------------------------------

                              =========================
                                 Release 01.06.0002
                              =========================
                              

Corrected issues:

   - Well display of web pages in asian languages.
   
  
Well known issues:
   
   - Under IE7 and IE8 browsers, the action on button "Save log" in Measurements,
   Event and System logs, does not open a popup window that allows to save the file,
   but diplays it directly in the browser.
   -> Workaround: Select File/Save as... in the browser menu.
   
   
--------------------------------------------------------------------------------

                              =========================
                                 Release 01.05.0001
                              =========================
                              

Corrected issues:

   - Trap with attached variables are only sent in V1 protocol.                          
   
   
--------------------------------------------------------------------------------
      
                              =========================
                                 Release 01.04.0007
                              =========================   


Improvements:

   - Add 2 traps in Dell UPS Mib:
       - trapCommunicationLost
       - trapCommunicationRestored.

   
Corrected issues:

   - English mistake corrected in Firmware upgrade help page(K-720).
   - Object "ipAdEntNetMask" of Mib-2 is updated with good value(K-738).
   - Remove older UPS alarms after an UPS core firmware upload(K-778).
   - Allow the shutoff and restart of UPS using UPS Control page even if 
   "Forced Shutdown and Restart of UPS" is disabled.
   - In NTP mode, upade NMC and UPS time only if the difference is upper than 10s.


Well known issues:

   - Weekly schedule feature : sometimes UPS stops or restarts 1 hour before when time mode
   is configured in NTP (K-573).


--------------------------------------------------------------------------------

                              =========================
                                 Release 01.03.0006
                              =========================  


Improvements:

   - A NMC Card reset is done when iGotoFirmwareUploadMode returns with errors.(K-754)
   This should avoid to lock the card and allow to upload a firmware at the end of the
   card restart.
   - No redirection to UPS Properties page on card Reset from System Settings.(K-725)
   This will not resolve completely this problem but it will reduce significatly it's
   occurence.   


Corrected issues:

   - Save logs is available when QuickTime is installed on computer(K-743).
   - Remove the IPv6 frame ethernet filter during the starting of the dual stack in the no Ipv6 setup.
   This filter might disturb the stack and perhaps caused the communications lost (K-729).


Well known issues:

   - Weekly schedule feature : sometimes UPS stops or restarts 1 hour before when time mode
   is configured in NTP (K-573).


--------------------------------------------------------------------------------
   
                              =========================
                                 Release 01.03.0005
                              =========================  

Improvements:

   - Add object physicalUPSOutpoutSwitchable in Dell UPS Mib
   - Add High Efficiency label in UPS Properties page when this mode is activated.

   
Corrected issues:

   - No immediate card reset on detection of SHUT desynchronisation, try 5 times to 
   resynchronise before reset(K-724).
   - Recovery of IP parameters (K-723).
   - Set minimum of Toggle duration to 10s to guarantee a correct UPS electrical swith off (K-721).
   - Help web pages updated with IpV6 and Force Reboot features (K-720).
   - Text of Force Reboot option modified with "Forced Shutdown and Restart of UPS" (K-706).
   - Good timestamp for UPS Metrics items (K-693).
   - All settings values are reinitialised after a Factory Reset (K-612).   
   - Accept user's message longer than 80 characters.   


Well known issues:

   - Weekly schedule feature : sometimes UPS stops or restarts 1 hour before when time mode
   is configured in NTP (K-573).
   - Communication lost with Dell UPS Management Software (K-729). Not reproduced at Montbonnot.
   - The firmware upload feature is not functional on UPS 5600 LI
   (revision  00.01.0025;00.01.0036).
   
       
--------------------------------------------------------------------------------

                              =========================
                                 Release 01.03.0004
                              =========================  

Corrected issues:

   - In UPS Control page, set the "Toggle Duration" default value to 10s to prevent
   the issue of none restart of UPS (K-666 + K-108).
   

Well known issues:

   - The firmware upload feature is not functional on UPS 5600 LI
   (revision  00.01.0021;00.01.0033).
   
       
--------------------------------------------------------------------------------
   
                              =========================
                                 Release 01.03.0003
                              =========================

Notes:

   - The firmware upload on UPS 5600 LI have not been tested yet with this firmware
   revision.
   
   
New features:

   - Firmware revision displayed on UPS LCD (K-164).
   - Add checkbox in Shutdown Parametrs page to enable or disable the "Force reboot"
   option (K-530).
   

Improvements:

   - Add 2 traps in Dell UPS Mib:
     - trapToBypassCommand
     - trapFromBypassCommand.

   
Corrected issues:

   - All settings values are reinitialised after a Factory Reset (K-612).
   - On UPS Properties page, battery status is "No battery" when the battery
   is disconnected.  
   - During UPS firmware upload, if mgeFtl application do not stop properly, the NMC
   card close the communication with it and restart the communication with UPS. 
   - After an UPS firmware upload, no reset is necessary. However for LI UPS with
   firmware revision 01.04.0001, mgeFtl closes with a "Connection error" at the end
   of upload.      
   - In Shutdown Parameters page, fields are not enabled or displyed if the Advanced
   parameters checkbox is not selected (K-613).
   - No much more Italian language displayed on web interface (K-618).
   - Root certificate shows the compagny name (K-636).
   - If we execute a "Save power down and reboot" with a "Toggle Duration = 0", the 
   UPS restarts (K-666 + K-108).
   - ABM state Discharging logged in event log when UPS is on battery. ABM state
   Resting is now detected and logged (K-671).
   - Modify notification message on "Overload Level 3 cleared" event : set "UPS
   overload Level3 cleared" in place of "UPS returns to normal load". This message
   is transfered to "Overload Level 3 cleared" event (K-672).
   
   
Well known issues:   

           
--------------------------------------------------------------------------------

                              =========================
                                 Release 01.03.0002
                              =========================

New features:

   - IPv6 compliant.
   - UPS firmware upload using mgeFtl application.
   

Improvements:

   - Add "physicalIdentReferenceNumber" object in Dell UPS Mib.
   

Well known issues:

   - After an UPS firmware upload, UPS and NMC have to be reseted.
   - During UPS firmware upload, if mgeFtl application do not stop properly, the NMC
   card could be locked, a reset is then necessary.
   - Action on Factory Reset doesn't reinitialize all Shutdown Parameters settings when 
   "Keep TCP/IP parameters" is selected.
   - On UPS Properties page, battery status is "Resting" or "Flaoating" when the battery
   is disconnected.
   
         
--------------------------------------------------------------------------------
                              
                              =========================
                                 Release 01.02.0013
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - After upgrading this release, make a Factory Reset of the card in order to have
   default settings (SNMP disabled and SSL enabled). Do that from System Settings page,
   using “Factory Reset” button.
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.


Corrected issues:
 
   - Card restarts normally after a shutdown sequence (Tracker 597).
   - Date and time of UPS and NMC are always synchronised in every time mode.
   

Well known issues:

   - Action on Factory Reset doesn't reinitialize all Shutdown Parameters settings when 
   "Keep TCP/IP parameters" is selected.
   - On UPS Properties page, battery status is "Resting" or "Flaoating" when the battery
   is disconnected.
    
   
--------------------------------------------------------------------------------

                              =========================
                                 Release 00.01.0012
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - After upgrading this release, make a Factory Reset of the card in order to have
   default settings (SNMP disabled and SSL enabled). Do that from System Settings page,
   using “Factory Reset” button.
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.


Improvements:

   - Modify the none active value of 3 objects in Mib DELL :
      - physicalUPSRuntimeToShutdown
      - physicalLoadSegment1RuntimeToShutdown
      - physicalLoadSegment2RuntimeToShutdown


Corrected issues:

   - The object "upsSecondsOnBattery" of UPS IETF Mib do not reseted to 0 when UPS is on battery (Tracker 545).
   - The synoptic corresponds to bypass one in High Efficiency mode (Tracker 526).
   - No more loss of Hostname and DNS server addresses during endurance test.
   

--------------------------------------------------------------------------------

                              =========================
                                 Release 00.01.0011
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - After upgrading this release, make a Factory Reset of the card in order to have
   default settings (SNMP disabled and SSL enabled). Do that from System Settings page,
   using “Factory Reset” button.
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.


Improvements:

   - Add 3 objects in Mib DELL :
      - physicalUPSRuntimeToShutdown
      - physicalLoadSegment1RuntimeToShutdown
      - physicalLoadSegment2RuntimeToShutdown


Corrected issues:

   - Modify default settings of Shutdown Parameters page to match with UPS ones.
   - In SSL mode, if a browser is still opened when the card is restarted, the 
   login/password is asked only one time (Tracker 528). 


Well known issue:

   - IP addresses of DNS could be lost after a restart.
   

--------------------------------------------------------------------------------

                              =========================
                                 Release 00.01.0010
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - After upgrading this release, make a Factory Reset of the card in order to have
   default settings (SNMP disabled and SSL enabled). Do that from System Settings page,
   using “Factory Reset” button.
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.


Improvements:

   - Workarround : if the card is blocked during IP stack initialisation, the card is
   automatically restarted(Tracker 460).
   
   
Corrected issues:
   
   - When Charger is disabled, the battery ABM charge status reports "Charger Disabled"
   (Tracker 116).
   - In Shutdown Parameters page, the Switch Off After field of Load Segments is controlled
   to be highier than the Shutdown Duration (Tracker 483).
   - Update Access Settings Help page to specify SSL enbled by default (Tracker 429).
   - Increase Secure Web Server stack to prevent firmware crashes(Tracker 489).      


Well known issue:

   - IP addresses of DNS could be lost after a restart.
   

--------------------------------------------------------------------------------

                              =========================
                                  Release 01.01.009
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - After upgrading this release, make a Factory Reset of the card in order to have
   default settings (SNMP disabled and SSL enabled). Do that from System Settings page,
   using “Factory Reset” button.
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.


Corrected issues:

   - SNMP acess disable by default (Tracker 394).
   - SSL mode enable by default (Tracker 395).
   
   
--------------------------------------------------------------------------------

                              =========================
                                  Release 01.01.008
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.


Improvements:

   - Notified applications are limited to 3 (Tracker 127).

   
Corrected issues:

   - Bypass frequency not supported by UPS and deleted from the synoptic (Tracker 349).
   - Redefinition of 3 traps of Dell Mib(Tracker 350):
      - trapLevel1Overload
      - trapLevel2Overload
      - trapLevel3Overload
   - Send trap trapBypassVoltageOutOfRange of Dell Mib (Tracker 388).      
   - Display UPS Serial Number without adding dashes (Tracker 322).
   - Implementation of new UPS names(Tracker 323).
   
   
--------------------------------------------------------------------------------

                              =========================
                                  Release 01.01.007
                              =========================

Notes:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P) with Bootloader release 1.3. 
   - This release is not IPv6 compliant, however the IP stack is a dual mode one and send
   Ethernet frames in IPv6 mode too.

Improvements:

   - In Dell Mib, addition of a new trap :
        - trapServiceBattery
   - When the battery is disconnected, the battery module appears in red in the synoptic
   (Tracker 125).
   - Retry to access the NTP server after initialisation when it is not reachable at
   initilisation time.
   
Corrected issues:

   - Set "physicalOutputPresentConsumption" object in good unit (Tracker 117).
   - In IETF Mib, upsSecondsOnBattery object increments when UPS in on battery (Tracker 197).
   - UPS synoptic displays in good color on Line Interactive (Tracker 109).
   - Send good trap numbers on "Utility failure test" and on "Shutdown test" (Tracker 126).
   - The display of battery status in UPS Properties page takes account of ABM status
   (Tracker 116).
   - In Maintenance Menu, removal of "No environnement sensor detected" sentence (Tracker 122).
   - Translations corrected (Trackers 119, 120, 121).
   - References to Network Shutdown Module Removed (Tracker 118, 128).
   - In synoptic page, add a maximum caracter per line to display all the data (Tracker 115).
   - Input Courant not supported by UPS and deleted from the synoptic (Tracker 110).
   - Help pages corrected.
   - Display UPS Serial Number with dashes.
   
   
--------------------------------------------------------------------------------
                              =====================
                                  Release 1.0b6
                              =====================

Note:

   - Do not upload this firmware release into Eaton NMC card (66102). This release
   is only compatible with Dell UPS Management Card (H910P). 


Improvements:

   - In Dell Mib, addition of 8 new traps :
        - trapInHighEfficiencyMode
        - trapReturnFromHighEfficiencyMode
        - trapRectifierOverload
        - trapRectifierOverloadOk
        - trapInverterOverload
        - trapInverterOverloadOk
        - trapBypassVoltageOutOfRange
        - trapBypassVoltageOutOfRangeOk
   - In Dell Mib, addition of "Scheduled" state for "physicalBatteryTestStatus"
   object.
   - Polling COPI inhibated to avoid application lock.
   
   
Corrected issues:

   - Provide event trapOnManualBypass of Dell Mib.
   - Modify the trigger of event trapABMOff of Dell Mib.
   - Set "physicalOutputCumulativeConsumption" object in good unit.
   - Application doesn't crash in Maintenance Menu.
   - Reading of MAC address in Flash is ok.


--------------------------------------------------------------------------------   
                              =====================
                                  Release 1.0b5
                              =====================

Improvements:

   - Removal of none used columns in Notified Applications page.

   
Corrected issues:

   - Display the correct serial number in About your UPS page.
   - Automatic language detection.


Well known issues:

   - Unable to read MAC address, always set to 0.
   - Application crashes in Maintenance Menu on "Modify Network settings" or 
   "Return to Default Configuration".
  
   
--------------------------------------------------------------------------------
                              =====================
                                  Release 1.0b4
                              =====================
   
   
Corrected issues:

   - Alarm translation in traditionnal chinese.
   - The change of SNMP Read Community name in Web inetreface is now taken into account.
   - Value of cumulative consumption corrected in UPS Metrics page.
   - Card technical level suppressed in About your UPS page.

Well known issues:

   - Dynamic measures window unreadable on small screen.
   - Automatic language detection is not functionnal for all NMC languages.
  
   
--------------------------------------------------------------------------------
                              =====================
                                  Release 1.0b3
                              =====================

Improvements:

   - Synoptic output arrow becomes red when the 2 load segments are in off state.
   - In Dell Mib, addition of 5 new objects :
        - physicalBatterySecondsRemaining
        - physicalLoadSegment1ShutdownAfterDelay
        - physicalLoadSegment1StartupAfterDelay
        - physicalLoadSegment2ShutdownAfterDelay
        - physicalLoadSegment2StartupAfterDelay
     and 4 new traps :
        - trapLoadSegment1Off
        - trapLoadSegment1On
        - trapLoadSegment2Off
        - trapLoadSegment2On
     The object physicalUPSAlarmsStatus listed only odd actve traps.
   - Removal of battery temperature, battery current and battery life time in pop-up
   window.   
   
   
Corrected issues:

   - Translation in traditionnal chinese.


Well known issues:

  - SNMP agent doesn't verify the Read Community name.
  
   
--------------------------------------------------------------------------------   
                              =====================
                                  Release 1.0b2
                              =====================


New features:

   - In IETF Mib, those objects are now implemented:
	      - upsSecondsOnBattery
        - upsInputLineBads
        - upsOutputSource
   - SNMP interface can be disabled from Access Settings page.


Improvements:

   - Bypass line of synoptic has been modified.
   - In Dell Mib, removal of following traps : 
        - trapABMCharging
        - trapABMFloating
        - trapABMResting
   - In Dell Mib, addition of 2 new objects :
        - physicalBatteryABMStatus
        - physicalBatteryTestStatus,  
   and modification of 2 traps :
        - trapABMOn(physicalBatteryABMStatus)
        - trapBatteryTestDone(physicalBatteryTestStatus)
        
        
Corrected issues:

   - "Execute" button of UPS Control page is now ok.
   - OIDs of Dell Mib Traps are right.
   - Mib-2 sysObjectID object contains Dell Mib OID.


Well known issues:


--------------------------------------------------------------------------------
                              =====================
                                  Release 1.0b1
                              =====================


   
Implemented features:

   - DELL look and feel.
   - UPS Metrics Web page.
   - Translation of Web pages in 9 languages.
   - Acquisition of all UPS Kiger HID objects.
   - Specific Dell UPS MIB.
   - IETF MIB for UPS.


Not yet implemented features:

   - In IETF Mib, those objects are not yet implemented:
	      - upsSecondsOnBattery
        - upsInputLineBads
        - upsOutputSource
        - upsTrapOnBattery
        - upsTrapAlarmEntryAdded
        - upsTrapAlarmEntryRemoved
   - SNMP interface can't be disabled.


Well known issues:

   - A click on "Execute" button of UPS Control page causes the reset of the card.


How to upgrade NMC EB version with the Dell 1.0b1 release:

   - The release 1.0b1 can't be directly upload on a NMC card with a firmware EB,
   the firmware EC must be upgraded first.
   - To upgrade the firmware, perform the following steps:
        - Insert a NMC card in a stable UPS (like EX 700 VA), and wait the end of
        initialisation.
        - Open a Web browser and enter the IP address of the card.
        - Click on the "Firmware upload" link.
        - Select the "eaton_nmc_EC.bin" file and click on "Upload".
        - Wait during card writing the firmware in Flash and the end of the restart.
        - Click on Refresh button of the browser.
        - Click on the "Firmware upload" link, and redo the same steps with the
        "dell_umc_1_0_b1.bin" file.
    - The version of a firmware can be checked in the "UPS Properties" page, on the
    "About your UPS" select.

EOF=
Download Driver Pack

How To Update Drivers Manually

After your driver has been downloaded, follow these simple steps to install it.

  • Expand the archive file (if the download file is in zip or rar format).

  • If the expanded file has an .exe extension, double click it and follow the installation instructions.

  • Otherwise, open Device Manager by right-clicking the Start menu and selecting Device Manager.

  • Find the device and model you want to update in the device list.

  • Double-click on it to open the Properties dialog box.

  • From the Properties dialog box, select the Driver tab.

  • Click the Update Driver button, then follow the instructions.

Very important: You must reboot your system to ensure that any driver updates have taken effect.

For more help, visit our Driver Support section for step-by-step videos on how to install drivers for every file type.

server: web4, load: 1.01