SNMPWEBCARD-AC4908/AC5540/6015 Firmware Change History
10/18/2008
-Added SNMP access control list
   A new net mask field has been added to allow for greater flexibility in defining what 
   IP’s are allowed SNMP access:

	Allow all
        IP = * 
	Net Mask = 0.0.0.0

	Allow specific
	IP = x.x.x.x
	Net Mask = 255.255.255.255

	Allow range
	IP = x.x.x.0
	Net Mask = 255.255.255.0

	Allow range
	IP = x.x.0.0
	Net Mask = 255.255.0.0

	Allow range
	IP = x.0.0.0
	Net Mask = 255.0.0.0


-The SNMPWEBCARD now has the ability to generate a configuration file based upon
 it’s current settings from an HTTP session.

	

	Login to the HTTP interface of the SNMPWEBCARD
	Go to the Settings-System menu 
	Click on the ‘Write Config’ button
	Click on the ‘View Config’ button
	Click on the edit menu of the browser and choose select all
	Right-click on the highlighted text and right-click and select copy
	Open notepad and paste the copied text
	Save the file as paconfig.ini
	Complete
	The file can now be FTP'd to other 12.04.045 SNMPWEBCARDS to configure
	them


-Added support to write events to a SYSLOG server

-Support 4 SYSLOG server entries

-Added RSS support

-Added support for protocol 4005

-Modifed the Battery Age over 3 year old event to a user configurable Battery
 Age Alarm Threshold, configurable via the Settings-System menu 

-Added the ability in the Telnet interface to view all of the event log enteries
 instead of just the first 20.


Known Issues:

-Upgrading to 12.04.0045 firmware will cause all user event, contact, and log
 information to be lost. 


1/8/2008 12.04.0040

-Added data logging support - Note: this is temporary and will be lost upon reboot

-Added support for command scheduling

-Added support for SNMP set action on events

-Allow for up to 32 SNMP trap destinations to be notified on an event

-Added support for 3014 UPS protocol

-Added default read and read write community strings

Known issues 12.04.0040
-Network shutdown requires the use of the new PowerAlert Network Shutdown Agent 


1/5/2007
-Requires PowerAlert version 12.04.0030 on a PC to utilize Remote Monitoring function to perform
 OS shutdown monitoring an SNMPWEBCARD.

-Modified the SNMP trap structures to differentiate a SNMP set event and a SNMP clear event

-Telnet support for configuration of SNMP NMS settings.

-Telnet support for email contact configuration.

-Telnet support for SMTP server configuration.

-Telnet support for configuration of email notification on an event.

-Telnet support for configuration of SNMP traps on an event.

-Telnet support for NTP server configuration.

-Default admin password is admin.

-Default guest password is guest.

-Added ability to reset terminal password via HTTP admin page.(x.x.x.x/admin.htm)

-Fixed bug where user "root" and password "TrippLite" granted you access to HTTP and Telnet.

-Support for Tripp Lite PDUMHNET devices (5001 protocol).

-Modified FTP firmware upgrade process to allow uploading both rom.bin and pwralert.dat in a single FTP
 session.

-Add support for load shedding upon loss of primary AC power and load ramping anytime primary AC power
 is applied on Tripp Lite autonomous devices with controllable outlets. Autonomous devices are devices
 that can be configured to load shed and ramp without the aid of a SNMPWEBCARD or PowerAlert PC software.
 Autonomous supported are:

 Product 	Series Number
SMART2200RMXL2U	AGSM5389
SMX2200RMXL2U	AGSM5392
PDUMH15AT	AGAC5558
PDUMH15ATNET	AGAC5558
PDUMH20AT	AGAC5559
PDUMH20ATNET	AGAC5559

-Support for load shedding on UPS systems with controllable outlets. These UPS are classified as
 non-autonomous an require a SNMPWEBCARD to present for any load shedding to take place upon loss of
 primary AC power. The SNMPWEBCARD will turn back on all outlets that were shed during a loss of primary
 AC power when primary AC power is reapplied.

-On any autonomous devices utilizing a SNMPWEBCARD, disconnect the network cable
 before utilizing the RS232 connection on the UPS.

-Added support for load shedding upon loss of primary AC on Tripp Lite non-autonomous devices with
 controllable outlets. Any outlets that were shed upon loss of primary AC power will be automatically
 turned back when power is restored.

-Added tlUpsOutlet table in TrippLite.MIB to allow ramping and shedding configuration and outlet control
 of devices with controllable outlets

NOTE: Upgrading from any prior version of SNMPWEBCARD FW to 12.04.0030 will cause a loss of all
      configuration settings.

Known issues:
Release - 12.04.0030
1) If utilizing Remote Monitoring function to shutdown over
   the network the PC's will need to have PowerAlert version 12.04.0030.
2) It takes several minutes for load shedding and ramping times to be saved to any autonomous device.
3) On SMART2200RMXL2U (communication protocol 3012) Auto-restart control commands do not work
4) On PDUMHAT devices, watchdog variables are not supported, but a watchdog group is displayed under the
  'Misc' button on the status menu.
5) On PDUMHAT devices, clicking on the battery button on the status menu no data is displayed since no
  battery variables are supported.
6) Under the Action-Control menu on PDUMHAT devices, the reboot device command is labeled as reboot UPS.



 4/25/2006 12.04.0019


- Modified the handling of PowerAlert Remote Monitors. If utilizing Remote Monitoring function to shutdown over
the network the PC's will need to have PowerAlert version 12.04.0019.

- Removed SNMP menu in Telnet session as SNMP settings not yet implemented in Telent menu.

- Fixed a problem with the Actions-Loads page not displaying correctly using Firefox.

- Fixed a problem with icons not displaying correctly using Firefox.

- Added functionality to allow for mutltiple system settings to be entered instead of requiring a reboot
  after each setting change.

- Fixed a problem that caused the card to continually send out change traps after a SNMP walk was performed 
  on the card.

- Fixed a problem with the with SNMP traps being sent out with incorrect OID string.

- Added device name to email notifications.

- Fixed a problem where some event traps were not being sent out.

- Added event action configuration for EnviroSense temperature, humidity and dry contact events.

- Fixed a problem in telent whereby there was no command to activate a UPS control that required parameters. There is 
  now a menu item to (A)ctivate the control.

10/12/2005 12.03.0024

- Fixed problem with event log events not displaying when the log size became to large in a HTTP session.

- Fixed problem with event log icons not properly being displayed when connected to the card via Firefox.

- Fixed problem when clicking save on the Settings-Events menu after making changes would not save the changes.

9/1/2005 - 12.03.0022 - Initial Release








Download Driver Pack

How To Update Drivers Manually

After your driver has been downloaded, follow these simple steps to install it.

  • Expand the archive file (if the download file is in zip or rar format).

  • If the expanded file has an .exe extension, double click it and follow the installation instructions.

  • Otherwise, open Device Manager by right-clicking the Start menu and selecting Device Manager.

  • Find the device and model you want to update in the device list.

  • Double-click on it to open the Properties dialog box.

  • From the Properties dialog box, select the Driver tab.

  • Click the Update Driver button, then follow the instructions.

Very important: You must reboot your system to ensure that any driver updates have taken effect.

For more help, visit our Driver Support section for step-by-step videos on how to install drivers for every file type.

server: web4, load: 0.79